| Model | unit | FA-08 |
| Rated heating capacity | KW | 27 |
| BTU | 92150 |
| Hot water supply | T/h | 0.58 |
| Average heating input power | KW | 5.9 |
| Rated heating input current | A | 28(220V) |
| 11(380V) |
| Max outlet water temp | ℃ | 60℃ |
| COP |
| 4.6 |
| Power | V/Hz | 220-240V/380-415V/50HZ |
| Nosie | dB(A) | 55 |
| Dimension | Width | mm | 1450 |
| Deepth | mm | 780 |
| Height | mm | 1050 |
| Unit weight | KG | 225 |
| Throttling type |
| Electronic expansion valves |
| Refrigerant |
| R410A/R32 |
| Working air temp range |
| – 20℃~45℃ |
| Compressor | Type |
| Scroll Copeland,.hitachi,panasonic |
| Security functions |
| Built-in protection device overheating protection, sequence protection, undervoltage protection, delay protect |
| Air source heat exchanger | Type |
| Finned heat exchange |
| Qty | piece | 1 or 2 |
| Fan type |
| Axial big twist Angle fan |
| Motor power | W | 50*2 |
| Hot water side heat exchange | Type |
| tube in shell heat exchanger/plate heat exchanger |
| Water flow | m3/H | 4.66 |
| Water pressure down | kPa | 34 |
| Pipe size | Inch | 1 |
| Water side max working pressure | kPa | 1000 |